ATS MX Contactor

MX350 Controller

Underfrequency Dropout for Source 1 and Source 2

45 - 59.9 Hz

Overfrequency Restore for Source 1 and Source 2

50 - 62.9 Hz

Delay NeutralTransition Time Delays (DT,DW)

0-10 minutes

SPECIFICATIONS

The MX350 controller is specifically designed for low voltage Automatic Transfer Switch (ATS) applications. The flexible control and communications options are ideal for any application. Integrated push buttons, graphical controls and LED indicators reduce external components and wiring in addition to providing local control and access to system information. Multiple communication protocols allow simple integration into monitoring and control systems.

    Controller Specifications

    Underfrequency Dropout for Source 1 and Source 2

    45 - 59.9 Hz

    Overfrequency Restore for Source 1 and Source 2

    50 - 62.9 Hz

    Delay NeutralTransition Time Delays (DT,DW)

    0-10 minutes

    Storage Temperature

    (-40˚C - 90˚C )

    Load Control Relay Contacts (1)

    rated for 10A @ 24VDC or 120VAC

    Delay for Engine Cool Down (U)

    0-60 minutes

    Communications Interface - Optional

    Serial RS-485 upt to 115.2 Kbps or TCP/IP (10/100 base-T)

    Overfrequency Dropout for Source 1 and Source 2

    50.1 - 63 Hz

    Source Sensing

    120 - 690 VAC +/- 1% of nominal voltage (+/- .05 Hz, +/-.5 A)

    Undervoltage Restore for Source 1 and Source 2

    85-100% of nominal

    Undervoltage Dropout for Source 1 and Source 2

    75-99% of nominal

    Control Power

    120 VAC

    Delay Transfer to Nonpreferred Source (W)

    0-5 minutes

    Underfrequency Restore for Source 1 and Source 2

    45 - 59.5 Hz

    Operating Temperature Ambient

    (-20˚C to 50˚C)

    Load Control Relay Contacts (2)

    0-259 minutes

    Overvoltage Restore for Source 1 and Source 2

    103 - 108% of nominal

    Overvoltage Dropout for Source 1 and Source 2

    105 - 110% of nominal

    Voltage Unbalance for Restore for Source 1 and Source 2

    4 to 19% of nominal

    Voltage Unbalance on Dropout for Source 1 and Source 2

    5 to 20% of nominal

    Technical Summary

    Transfer Type

    Application Dependent

    Rating Range

    Switch Dependent

    Switch Type

    Application Dependent

    • Status LEDS for:
      • Transfer Inhibit
      • Active Alarms
      • Source 1 and 2 Availablity
      • Source 1 and 2 Connected
      • Time Delay Active
    • Graphical Display:
      • Color graphical display with USB Calibration/programming port and Embedded Help
      • Displays 256 time-tagged events with 1 ms resolution
      • Monitors over/under frequency, voltage conditions, frequency imbalance, and phase rotation
      • Provided detailed outage,test,and diagnostic reports
    • Ranges of Controls / Metering:
      • Programmable generator exerciser
      • Synchroscope
      • Contacts for Source 1 and Source 2 position indication as well as remote load test signals, and engine start delay
      • Source 1 and Source 2 In-phase monitor
      • Neutral, Engine Start, and Engine stop time delay timers
    • Testing and Certification
      • Conforms to EN 60947-1, EN 60947-6-1, EN 60255-26 (EN 50263), EN 5502 / CISPR22 / EN 61000-6-2 / EN 61000-6-4
      • Tested in accordance with:
        IEC 60068-2-30
        IEC 60068-2-1
        IEC 60068-2-2
        IEC 60255-22-1
        IEC 60255-22-2
        IEC 60255-22-3
        IEC 60255-22-4
        IEC 60255-22-5
        IEC 60255-22-6
        IEC 60255-25
        IEC 60529; IP54 (front),IP20(back)
        IEC 61000-4-11
      • Quality System:
        Manufactured under an ISO 9001 Registered Program

    • Option Package A:
      • Four (4) programmable inputs and four (4) outputs assignable to additional ATS features
      • Expanded diagnostics, high-speed 256 event capture, 365 days
      • Monitoring Software (local or remote), USB interface for uploading and downloading setup parameters
      • Full function ATS control with full sensing and control capabilities
      • Full complement of programmable ATS control switches AUTO / MAN, Preferred Source selector,Commit / No Commit Xfer, Transition Mode Select for Closed Transition switch models)
    • Option Package B:
      • Waveform capture, ten (10) channels, up to 256 cycles each sixteen (16) samples / sec.
      • Ten (10) customer programmable digital and ten (10)analog alarms.
      • Includes Option Package A features, plus
      • Auto Load Shed with voltage, frequency and kW triggers.
      • Twenty (20) channel data logger, customer configurable sample period from one (1) cycle to sixty (60) minutes.
    • Option Package C:
      • Includes Option B features, plus
      • Four (4) additional inputs and outputs (totaling eight (8) in & eight (8) out)
    • Option Package D:
      • Customized user control logic
      • Includes Option Package C features, plus
      • Four (4) additional inputs and outputs (totaling twelve (12) in & twelve (12) out)
    • Option Package M:
      • Configuration for Manual Operation only (Non-Automatic)

    WHY CHOOSE EMPIRE

    • Machines built tough and ready to run in rugged applications

    • Trusted advisors to help you find and maximize your equipment

    • Wide inventory of rental equipment that lets you try before you buy

    • Full service and support to ensure performance and longevity