THIS IS MY SELECT

Rating

1900 ekW (2375 kVA) Continuous

Frequency

50Hz

Voltage

400 V

SPECIFICATIONS

    Dimensions

    Width - Without Chassis

    96 in

    Height - Without Chassis

    114 in

    Length - Without Chassis

    480 in

    Weight - Without Chassis, With Lube Oil and Coolant

    77,780 lb

    Engine

    Engine

    Cat G3516H

    Fuel

    Natural Gas

    Generator Set

    Rating

    1900 ekW (2375 kVA) Continuous

    Frequency

    50Hz

    Voltage

    400 V

    • Engine
      • G3516H, V16, 4-stroke-cycle, gas engine.
        Operates on 24.10 to 93.95 MJ/Nm3 (615 to 2386 btu/ft3) dry pipeline natural gas.
        Turbocharged Separate Circuit Aftercooled.
    • Generator
      • Double bearing SR5 1866 frame, brushless, form wound, 12-lead design, permanent magnet excited, three-phase, with Cat IVR, Class H insulation operating at Class F temperature.
        Stator and Bearing temperature monitoring and anti-condensation space heaters.
    • Containerized Module
      • 40' ISO high cube container, 9-high stack CSC certified.
        Sound attenuated 79 dB(A) @ 7 m (23 ft)
        Sound attenuated air intake louvers and 2lockable personnel doors with panic release
        LH and RH engine service doors integrated intocontainer side walls
        3” ANSI flange customer fuel connection
    • Cooling
      • Standard cooling provides 40⁰C (104⁰F) ambient capability with 500mg/Nm3 NOx at 100% Continuous rating before derate, @ 500m
    • Generator Controls And Protection
      • On Package EMCP 4.3 Control Panel System
        Offers engine and generator monitoringand protection, voltage regulation with Cat IVRimproves transient response performance.
        Controls provide auto paralleling AGC-4 controller, load sharing, VFDcontrol, and primary generator protection for greaterversatility, package utilization and monitoring.
    • Modes of Operation
      • Provides for single unit stand-alone operation,island mode paralleling and load sharing withother power modules, and single unit-to-utilitymode paralleling for base load control
    • Lube Oil Make-Up System
      • Oil pan-mounted oil level regulator and 114 L (30 gal) oil tank
        Low level annunciation