THIS IS MY SELECT
XQ1140 T4 Final - Diesel
Rating Prime
910 ekW (1136 kVA)
Frequency
60 Hz
Voltage
120 - 600V
SPECIFICATIONS
XQ1140 Rental Power Generator Set.
Dimensions
Height - Without Trailer
114 in
2,896 mm
Length - Without Trailer
480 in
12,192 mm
Width - Without Trailer
96 in
2,438 mm
Weight with Lube Oil and Coolant, Without Trailer
50,107 lb
22,728 kg
Engine
Engine
C18 ACERT™
Fuel
Diesel
Fuel Consumption
100% Load 60Hz
66.4 gal/hr
252 l/hr
75% Load 60Hz
52.4 gal/hr
198 l/hr
50% Load 60Hz
38 gal/hr
144 l/hr
100% Load 60Hz
71.8 gal/hr
272 l/hr
75% Load 60Hz
56.6 gal/hr
214 l/hr
50% Load 60Hz
41 gal/hr
156 l/hr
Generator Set
Rating Prime
910 ekW (1136 kVA)
Frequency
60 Hz
Voltage
120 - 600V
Rating Standby
1000 ekW (1250 kVA)
Noise rating (with enclosure)
Sound Power @ 7 meters (23 feet) @ All Ratings
76 dB(A)
- Cat C18 Diesel Engines
- Two Cat C18 Diesel Engines
- Reliable, rugged, durable design
- EPA Tier 4 Final and CARB Emissions Certified
- Turbocharged Aftercooled
- Aftertreatment module.
DEF System
- Alternator and Alternator attachments
- 3 Phase, brushless, 12 lead, Permanent Magnet Excited
- LC6134G Frame
- Anti-condensation space heaters
- Integrated voltage regulator (IVR) with VAR/PF control
- Sized for 105°C temperature rise at 40°C ambient
- Control Panels
- Dual EMCP 4.4 Generator-Set Mounted Digital Controllers
- Externally accessible Color Touch-Screen HMI Control Center
- Manual and automatic paralleling capability
- Governing system
- Electrical governing system ADEM™ A4
- Cat Connect remote monitoring
- Provides package monitoring and management
- Cooling System
- Vertically mounted radiator with vertical airdischarge from the container
- Provides 47°C ambient capability at Prime rating
- Charging / Starting System
- UL Listed and CSA Certified 240V, 20 Amp battery charger
- Charging alternator; 24V-80A, heavy duty withintegral regulator and belt guards
- Solar maintainer for batteries
- Single electric starting motor, 24V per engine
- Fuel System
- 630-gal (2385 L) double-wall fuel tank, UL 142and ULC 601 Listed and complies with TransportCanada requirements, internal and external fuel fill
- Fuel tanks connected by fuel transfer system withfilter to allow both engines access to all fuel on-board
- Primary and secondary fuel filters
- Fuel cooler
- Air inlet system
- Heavy-duty air element, canister type
- Distribution
- Externally-accessible, Vibration Isolated, 3600A Frame, 1000 Ka, IC, 3-pole electrically operated breaker with lock out tag out provision.
- Busbar connections
- Dual customer connections
- Sound Attenuated Container
- 40' ISO high cube container
- Sound level is 76 dB(A) at 7 meters per SAEJ1074 measured at 75% prime load
- Sound attenuated air intake louvers and fivelockable personnel doors with panic release
- Lube System
- Pump, integral oil cooler, lube oil, filter, filler anddipstick, and oil sampling valve
- Oil drain line with internal brass ball valve routedto connection point accessible from exterior
- General
- Factory tested and inspected
- Full manufacturer’s warranty
- UL, NEMA, ISO, and IEEE standards
- Trailer
- Two-axle, air-ride chassis with anti-lock brake
system
- Two-axle, air-ride chassis with anti-lock brake
Similar Models
WHY CHOOSE EMPIRE
-
Machines built tough and ready to run in rugged applications
-
Trusted advisors to help you find and maximize your equipment
-
Wide inventory of rental equipment that lets you try before you buy
-
Full service and support to ensure performance and longevity