THIS IS MY SELECT
Switchgear and Paralleling Controls
Cat XLM Switchgear
Configuration
Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications
Modes of Operation
Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
Application
LV and MV ( 208V - 38 kV
Request a Quote
SPECIFICATIONS
The Emergency Transfer and Load management (XLM) product supports transfer between the utility source and generator bus and allows for sustained parallel operation with the utility for load management applications.
Environmental Parameters
Certifications
IBS, CBC, UBC & OSHPD Certified
Control Panel Enclosure
NEMA 1 or NEMA 3R, Freestanding Construction
Operating Temperature
0 degrees to 50 degrees C
Storage Temperature
-20 degrees C to +60 degrees C
Low Voltage Standards
NEMA SG-5, CSA, ANSI C37.51, ANSI C37.20.1, UL 1558 or UL 891, NFPA 110, NFPA 99 and NFPA 70
Medium Voltage Standards
NEMA SG-5, ANSI / IEEE C37.20.2, CSA-C22.2 No. 31-M89, EEMAC G8-3.2, NFPA 70, NFPA 99 and NFPA 1110
Generator Protective Devices
ANSI Protective Devices
15/25, 27/59, 81 O/U, 32, 40, 50, 51
Technical Summary
Configuration
Configurable PLC based switchgear capable of controlling and monitoring multiple generator sets, tie, utility and load breakers for utility paralleling applications
Modes of Operation
Emergency Standby, Utility Import/Export, Peak shaving, and base load operations with redundant controls and components. Closed transition to/from generator power
Application
LV and MV ( 208V - 38 kV
Utility Protective Devices
ANSI Protective Devices
15/25, 27/59, 81 O/U, 32, 40, 47, 50, 51, 86
- Generator Demand Priority Control
- Automatically match the on-line generator capacity to the loads, and avoid unnecessary operation of generator sets.
- Data Table Interface
- Accommodates interface with a building management system for monitoring all system parameters via Modbus RTU or TCP
- Supplemental Hardware Synchronization check relay (ANSI 25 Device)
- Provides additional discrete synchronization protection
- Remote Power Monitoring System
- To monitor breaker status, alarms, metering and other operating parameters