ATS TruOne - TruControl

Cat® CG – ATS for general purpose applications

Rating Range

30 - 3000 A

Transfer Type

Open Transition (CG), Delayed Transition (CGD)

Switch Type

Contactor

SPECIFICATIONS

The CG Series – Contactor-type, Open Transition (CG) and Delayed Transition (CGD) ATS for general purpose applications offers functionality for critical emergency power applications in commercial and light industrial applications, with an enhanced feature set and LCD HMI interface.

The CG provides a durable mechanism that is tested up to 6,000 cycles. Electrical system parameters are set via the HMI and pre-configuration file upload is available via USB or Bluetooth connection.

    System Information

    Product nodes

    30, 60, 100, 125, 160, 200, 260, 400, 600, 800, 1000, 1200, 1600, 2000, 2600, 3000A

    Rated Voltage and Frequency

    200-480VAC, 50/60 Hz

    Phase system

    Single and Three (three phase only >600A)

    Number of poles

    2, 3 and 4 (3 & 4 pole only >600A)

    Neutral configuration

    Optional Solid or Switched neutral

    Product type

    Open transition (I-II), Delayed Transition (I-O-II)

    Technical Summary

    Rating Range

    30 - 3000 A

    Transfer Type

    Open Transition (CG), Delayed Transition (CGD)

    Switch Type

    Contactor

    • Control
      • LCD + keys
      • Voltage and frequency settings: Pick up and Drop out
      • Time Delay Settings: Override momentary, Transfer, Generator stop, Center-OFF, Pre-transfer, Post-transfer, Elevator Pre-signal, Elevator Post-signal, and Load shead
      • Source failure detections: No Voltage, Under/Over Voltage, Phase missing, Voltage unbalance, Invalid frequency, and Incorrect phase sequence
    • Additional Features
      • LED indications for ATS, S1 and S2 status
      • Open transition - Standard digital inputs/outputs (1/1)
      • Delayed transition - Standard digital inputs/outputs (2/1)
      • Programmable digital inputs/outputs
      • Auto config (voltage, frequency, phase system)
      • Source priority (Source 1/2, No priority)
      • Manual re-transfer
      • In-phase monitor (synchro check)
      • Genset exercising: on-load, off-load
      • Load shedding
      • Real time clock
      • Event log

    • Accessories
      • Auxiliary contacts for position indication
      • Additional digital input/output contacts (adding up to 6 each)
      • 12-24 VDC aux supply module for controller
      • Communication modules
    • Connectivity Capability
      • Modbus RTU (RS-485)
      • Modbus/TCP
      • Profibus DP
      • ProfiNet Yes
      • DeviceNet
      • Ethernet IP