THIS IS MY SELECT
C18 Generator Set
Maximum Rating
600 ekW
Minimum Rating
455 ekW
Emissions/Fuel Strategy
U.S. EPA Cert., Tier 2
SPECIFICATIONS
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Engine Specifications
Engine Model
C18 ATAAC, I-6, 4-Stroke Water-Cooled Diesel
Bore
5.71 in
145 mm
Stroke
7.2 in
183 mm
Displacement
1,106.4 l
18.1 in³
Compression Ratio
14.5:1
Aspiration
Air to Air Aftercooled
Fuel System
Electronic unit injection
Governor Type
Adem™A4
Generator Set Dimensions
Length - Maximum
5,550 in
218.5 mm
Width - Maximum
80.9 in
2,056 mm
Height - Maximum
107.8 in
2,737 mm
Generator Set Specifications
Maximum Rating
600 ekW
Minimum Rating
455 ekW
Emissions/Fuel Strategy
U.S. EPA Cert., Tier 2
Voltage
208 to 600 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby, Prime
- Air Inlet
- Air cleaner
- Air Inlet System
- Turbocharger
- Light duty air cleaner
- Aftercooler core
- Cooling
- Caterpillar extended life coolant
- Fan drive, battery charging alternator drive
- Coolant drain line with valve
- Radiator and cooling fan with guard
- Package mounted radiator
- Exhaust
- Exhaust flange outlet
- Exhaust System
- Stainless steel exhaust flex gaskets, raincap and SAE exhaust
flange for customer use - shipped loose
- Stainless steel exhaust flex gaskets, raincap and SAE exhaust
- Fuel System
- Standard 8 hour open set fuel tank
- Fuel
- Secondary fuel filters
- Fuel priming pump
- Primary fuel filter with integral water separator
- Generator and Attachments
- Matched to the performance and output characteristics of Cat engines
- Segregated low voltage (AC/DC) wiring panel
- Power center, IP22
- A Frame generator - IP21 protection
- Integrated voltage regulator (IVR)
- Mandatory option circuit breaker, IEC, 3 pole, mounted in power centre
- Integrated voltage regulator (IVR)
- Generator
- IP23 Protection
- Matched to the performance and output characteristics of Cat engines
- Load adjustment module provides engine relief upon load impact and improves load acceptance and recovery time
- Power Termination
- Busbar
- Control System
- GCCP 1.2
- Governing System
- Cat electronic governor (ADEM A4)
- Control Panel
- EMCP 4 Genset controller
- Lube System
- Lubricating oil
- Oil drain valves
- Mounting System
- Captive linear vibration isolators between base and engine-generator.
includes lifting provisions and termination points for coolant
and lube oil drain lines
- Captive linear vibration isolators between base and engine-generator.
- Mounting
- Rubber vibration isolators
- Starting/Charging
- 24 Volt battery with rack and cables
- 24 volt starting motor
- Batteries
- General
- Engine and alternator pre-paint, Caterpillar yellow
- Paint - Caterpillar yellow except rails and radiators gloss black
- Air Inlet System
- Single element air cleaner
- Dual element air cleaner
- Exhaust
- Industrial, residential, critical mufflers
- Generator
- Oversize and premium generators
- Excitation: [ ] Permanent magnet excitation (PMG) Excited (PM) [ ] Internally Excited (IE)
- Anti-condensation heater
- Power Termination
- Circuit breakers, UL listed
- Circuit breakers, IEC compliant
- Circuit breakers
- 3 Pole (IEC-100% rated) Circuit breakers - Motorised
- 4 Pole (IEC-100% rated) Circuit breakers - Motorised
- Shunt trip for IEC breaker
- Power terminal strip
- Circuit breaker (IEC) Auxiliary contacts
- 3 Pole (IEC-100% rated) Circuit breakers - Package mounted
- Padlockable circuit breaker device
- 4 Pole (IEC-100% rated) Circuit breakers - Package mounted
- Control Panels
- Remote monitoring software
- Load share module
- Local & remote annunciator modules
- GCCP 1.2, GCCP 1.5
- Digital I/O module
- Control System
- Local alarm modules
- Volt free contact
- Local alarm horn
- Remote annunciator module
- Oil temperature displays
- Protective devices: Earth fault relay - earth leageage Ground fault relay - Overload shutdown via breaker - Low fuel level alarm - Low fuel level shutdown - High fuel level alarm - Fuel level sensor
- GCCP 1.5
- Cooling System
- Low coolant temperature alarm
- Radiator duct flange
- Enclosures
- Sound attenuated enclosures
- Starting/Charging
- Jacket water heater
- Battery chargers
- Heavy duty starting system
- Oversize batteries
- Charging alternator
- Exhaust System
- 8 and 10 inch GP flanges
- 8 and 10 inch elbow kits
- Engine mounted muffler
- 10, 25 and 35 end in / end out mufflers
- Manifold and turbocharger guards
- Fuel System
- Manual fuel transfer pump
- Fuel transfer system
- Integral - Dual wall fuel tank base
- General
- Sound attenuated, weather protective or high ambient weather protective enclosure
- Integral & sub-base UL listed dual wall fuel tanks
- CSA Certification
- Automatic transfer switches (ATS)
- The following options are based on regional and product configuration:
- Single or dual wall sub-base fuel tanks
- EU Certificate of Conformance (CE)
- EEC Declaration of Conformity
- UL 2200 package
- Single or dual wall integral fuel tanks
- Seismic Certification per applicable building codes: IBC 2000, IBC 2003, IBC 2006, IBC 2009, CBC 2007
- Narrow, wide or skid base
- Enclosures: Sound attenuated, weather protective
- Generator and Attachments
- Space heaters
- A Frame CIP generator
- Permanent magnet excitation (PMG)
- LC frame generator
- A Frame oversize generator
- Ingress protection
- LC frame CIP generator
- LC frame oversize generators
- Lube System
- Manual sump pump
- Starting and Charging
- Battery disconnect switch
- Jacket water heaters
- 5 Amp Battery charger
Related Attachments
Similar Models
WHY CHOOSE EMPIRE
-
Machines built tough and ready to run in rugged applications
-
Trusted advisors to help you find and maximize your equipment
-
Wide inventory of rental equipment that lets you try before you buy
-
Full service and support to ensure performance and longevity