THIS IS MY SELECT

Diesel Generator Sets

C32 | 1500 kVA 50Hz Generator Set

Maximum Rating

1500 kVA

Minimum Rating

910 kVA

Emissions/Fuel Strategy

Low Fuel, Low Emissions

SPECIFICATIONS

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.Producing reliable power from 910 kVA to 1500 kVA at 50 Hz, our C32 diesel generator sets are made to meet your mission critical, continuous, standby and prime applications. We've designed each to ISO 8528-5 transient response requirements and to accept 100 percent rated load in one step. Generator sets range from low fuel consumption to low emissions systems. Seismic certification is also available for select models, ensuring you maintain power after unexpected disturbances. Our integrated control system, including ATS and switchgear, protects your power supply and keeps you connected through on-site and remote monitoring options. We offer easy-to-use EMCP control panel options, combining your management and diagnostic tools in one. The EMCP 4.4 controller provides multi-generator set paralleling capability, giving you the ability to add generator sets to match your growing power requirements. Browse a broad range of accessories and bolt-on system expansion attachments. Find flexible packaging to fit unique spatial requirements and environmental conditions. Our C32 generator sets are made for demands, so you can make yours.

    Engine Specifications

    Engine Model

    C32 TA, V-12, 4-Stroke Water-Cooled Diesel

    Bore

    5.71 in

    Stroke

    6.38 in

    Displacement

    1,958.86 in³

    Compression Ratio

    15.0:1

    Aspiration

    Turbocharged, Air to Air Aftercooled

    Fuel System

    MEUI

    Governor Type

    Adem™A4

    Generator Set Dimensions

    Length - Minimum

    164 in

    Length - Maximum

    176.6 in

    Width - Minimum

    66.3 in

    Width - Maximum

    87.8 in

    Height - Minimum

    85.1 in

    Height - Maximum

    86.4 in

    Dry Weight - Genset (minimum)

    14,700 lb

    Dry Weight - Genset (maximum)

    17,855 lb

    Generator Set Specifications

    Maximum Rating

    1500 kVA

    Minimum Rating

    910 kVA

    Emissions/Fuel Strategy

    Low Fuel, Low Emissions

    Voltage

    400 to 3300 Volts

    Frequency

    50 Hz

    Speed

    1500 rpm

    Duty Cycle

    Standby, Mission Critical, Prime, Continuous

    • Air Inlet System
      • Single element canister type with service indicator
    • Control Panel
      • GCCP Control panel
      • Warning shutdowns
      • Programmable protective relaying functions
      • Communications
      • Digital indicators
      • Control features
    • Cooling System
      • Radiator fan and fan drive
      • Coolant drain line with valve
      • ATAAC
      • Caterpillar extended life coolant
      • Fan and belt guards
      • Low coolant level sensor
    • Exhaust
      • 203 mm (8 in) ID round flanged outlet
      • Exhaust manifold - dry
    • Fuel System
      • Fuel cooler
      • Secondary fuel filters
      • Primary fuel filter with water separator
      • Fuel priming pump
    • Generators and Attachments
      • Permanent magnet excitation (PMG)
      • Reactive droop
      • Integrated voltage regulator (IVR)
      • 6 Lead
      • Salient pole
      • Class H temperature rise at 40C ambient
      • Busbar connections, top center mounted, top cable entry
      • Internal excitation (IE)
      • 3 Phase brushless
      • Winding temperature detectors
      • IEC standard hole pattern
      • NEMA Class H insulation
    • Governing System
      • ADEM(tm) A4
    • Mounting System
      • Rails - engine/generator/radiator mounting
      • Rubber anti-vibration mounts
    • Lube System
      • Fumes disposal
      • Integral lube Oil cooler
      • Oil filter, filler and dipstick
      • Gear type lube oil pump
      • Lubricating oil
      • Oil drain lines and valve
    • Power Termination
      • Busbar
    • Starting / Charging System
      • Battery disconnect switch
      • 45 Amp Charging alternator
      • 24 Volt electric starting motor
      • Battery, rack and cables
    • General
      • SAE standard rotation
      • RH service
      • Flywheel and flywheel housing-SAE
      • Caterpillar yellow with high gloss black rails & radiator

    • Air Inlet System
      • Standard air cleaners
      • Dual element air cleaner
      • Heavy duty air cleaner
    • Circuit breakers
      • Shrouds
      • Enclosures - Control packaging
      • 1600, 2000, 2500 and 3200 Amp, 3 Pole, IEC-Rated Circuit breakers
      • Cable supports
      • Circuit breaker wiring groups
      • Power connection covers
      • Center posts busbars
      • 800, 1600, 2000, 2500 and 3200 Amp, 4 Pole, IEC rated Circuit breakers
      • 400, 800, 1200, 1600, 2000, 2500 and 3000 Amp, 3 Pole, UL-100% Rated Circuit breakers
    • Control Panels
      • GCCP Control panel
    • Cooling System
      • High ambient radiator
      • Extended life coolant
      • Radiator duct flange
      • Standard radiator
      • Certified radiator
    • Enclosures
      • AC Panel, outlets and lights
      • Premium sound attenuated enclosure
      • Enclosure louvres - fixed and motorized
      • Enclosure fuel tank options
      • Color options
      • Panel bracket
      • Sound attenuated enclosure
      • DC lighting package
      • Cold weather bundle
    • Exhaust System
      • All C32 engines have 203 mm (8 in) exhaust outlets
      • Mufflers
      • Elbow mounting kit
      • Flange and exhaust expanders
      • Flexible fittings
      • Guard and shield system
      • Flanges
      • Exhaust through the wall kit
    • Generator and Attachments
      • Medium voltage generators
      • Low voltage generators
    • Lube System
      • Oil pan
      • Prelube manual sump pump
      • Oil level regulator
    • Mounting System
      • IBC vibration isolators
      • Spring type vibration isolators
      • Standard package isolators
      • Mounting base types
    • Power Termination
      • Circuit breakers, IEC compliant
      • Circuit breakers, UL listed
    • Power Connections
      • Center post busbars
      • Neutral grounding connection
      • Low voltage connection cables
    • Starting / Charging System
      • Electric starting motor - Standard/heavy duty
      • Space heater
      • Standard 24 volt open package battery set - Dry
      • 10 Amp Battery charger
      • 20 Amp Battery charger
      • Jacket water heater
      • 10 Amp enclosure Battery charger
      • 35 Amp Battery charger
    • Special Tests / Reports
      • Standard engine test
      • OSHPD seismic Certifications
      • Generator test report
      • Custom generator TVA report
      • Standard genset Torsional Vibration Analysis (TVA) report
      • IBC seismic Certifications
      • PGS Test report @ 0.8 power factor
      • PGS Test report @ 1.0 power factor
      • CSA test and certification
    • General
      • Special paint
      • US aid emblem

    Similar Models

    WHY CHOOSE EMPIRE

    • Machines built tough and ready to run in rugged applications

    • Trusted advisors to help you find and maximize your equipment

    • Wide inventory of rental equipment that lets you try before you buy

    • Full service and support to ensure performance and longevity

    YOU MIGHT ALSO BE INTERESTED IN