THIS IS MY SELECT

Diesel Generator Sets

C32 | 1250 kVA 50 Hz Generator Set

Maximum Rating

1500 kVA

Minimum Rating

910 kVA

Emissions/Fuel Strategy

Low Fuel, Low Emissions

SPECIFICATIONS

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.Producing reliable power from 910 kVA to 1500 kVA at 50 Hz, our C32 diesel generator sets are made to meet your mission critical, continuous, standby and prime applications. We've designed each to ISO 8528-5 transient response requirements and to accept 100 percent rated load in one step. Generator sets range from low fuel consumption to low emissions systems. Seismic certification is also available for select models, ensuring you maintain power after unexpected disturbances. Our integrated control system, including ATS and switchgear, protects your power supply and keeps you connected through on-site and remote monitoring options. We offer easy-to-use EMCP control panel options, combining your management and diagnostic tools in one. The EMCP 4.4 controller provides multi-generator set paralleling capability, giving you the ability to add generator sets to match your growing power requirements. Browse a broad range of accessories and bolt-on system expansion attachments. Find flexible packaging to fit unique spatial requirements and environmental conditions. Our C32 generator sets are made for demands, so you can make yours.

    Engine Specifications

    Engine Model

    C32 TA, V-12, 4-Stroke Water-Cooled Diesel

    Bore

    5.71 in

    Stroke

    6.38 in

    Displacement

    1,958.86 in³

    Compression Ratio

    15.0:1

    Aspiration

    Turbocharged, Air to Air Aftercooled

    Fuel System

    MEUI

    Governor Type

    Adem™A4

    Generator Set Dimensions

    Length - Minimum

    164 in

    Length - Maximum

    176.6 in

    Width - Minimum

    66.3 in

    Width - Maximum

    87.8 in

    Height - Minimum

    85.1 in

    Height - Maximum

    86.4 in

    Dry Weight - Genset (minimum)

    14,700 lb

    Dry Weight - Genset (maximum)

    17,855 lb

    Generator Set Specifications

    Maximum Rating

    1500 kVA

    Minimum Rating

    910 kVA

    Emissions/Fuel Strategy

    Low Fuel, Low Emissions

    Voltage

    400 to 3300 Volts

    Frequency

    50 Hz

    Speed

    1500 rpm

    Duty Cycle

    Standby, Mission Critical, Prime, Continuous

    • Air Inlet System
      • Single element canister type with service indicator
    • Control Panel
      • GCCP Control panel
      • Control features
      • Programmable protective relaying functions
      • Digital indicators
      • Warning shutdowns
      • Communications
    • Cooling System
      • Fan and belt guards
      • Radiator fan and fan drive
      • ATAAC
      • Coolant drain line with valve
      • Caterpillar extended life coolant
      • Low coolant level sensor
    • Exhaust
      • Exhaust manifold - dry
      • 203 mm (8 in) ID round flanged outlet
    • Fuel System
      • Primary fuel filter with water separator
      • Fuel priming pump
      • Secondary fuel filters
      • Fuel cooler
    • Generators and Attachments
      • Integrated voltage regulator (IVR)
      • Permanent magnet excitation (PMG)
      • 3 Phase brushless
      • Reactive droop
      • Internal excitation (IE)
      • NEMA Class H insulation
      • Class H temperature rise at 40C ambient
      • Salient pole
      • Winding temperature detectors
      • 6 Lead
      • IEC standard hole pattern
      • Busbar connections, top center mounted, top cable entry
    • Governing System
      • ADEM(tm) A4
    • Mounting System
      • Rails - engine/generator/radiator mounting
      • Rubber anti-vibration mounts
    • Lube System
      • Oil drain lines and valve
      • Integral lube Oil cooler
      • Fumes disposal
      • Lubricating oil
      • Oil filter, filler and dipstick
      • Gear type lube oil pump
    • Power Termination
      • Busbar
    • Starting / Charging System
      • 24 Volt electric starting motor
      • Battery, rack and cables
      • Battery disconnect switch
      • 45 Amp Charging alternator
    • General
      • Caterpillar yellow with high gloss black rails & radiator
      • RH service
      • Flywheel and flywheel housing-SAE
      • SAE standard rotation

    • Air Inlet System
      • Dual element air cleaner
      • Heavy duty air cleaner
      • Standard air cleaners
    • Circuit breakers
      • 1600, 2000, 2500 and 3200 Amp, 3 Pole, IEC-Rated Circuit breakers
      • Enclosures - Control packaging
      • Cable supports
      • Center posts busbars
      • Circuit breaker wiring groups
      • Power connection covers
      • Shrouds
      • 400, 800, 1200, 1600, 2000, 2500 and 3000 Amp, 3 Pole, UL-100% Rated Circuit breakers
      • 800, 1600, 2000, 2500 and 3200 Amp, 4 Pole, IEC rated Circuit breakers
    • Control Panels
      • GCCP Control panel
    • Cooling System
      • Radiator duct flange
      • Certified radiator
      • High ambient radiator
      • Standard radiator
      • Extended life coolant
    • Enclosures
      • Enclosure fuel tank options
      • Sound attenuated enclosure
      • Enclosure louvres - fixed and motorized
      • Color options
      • AC Panel, outlets and lights
      • Premium sound attenuated enclosure
      • Cold weather bundle
      • Panel bracket
      • DC lighting package
    • Exhaust System
      • Exhaust through the wall kit
      • Flange and exhaust expanders
      • Flanges
      • Guard and shield system
      • All C32 engines have 203 mm (8 in) exhaust outlets
      • Elbow mounting kit
      • Mufflers
      • Flexible fittings
    • Generator and Attachments
      • Low voltage generators
      • Medium voltage generators
    • Lube System
      • Oil pan
      • Prelube manual sump pump
      • Oil level regulator
    • Mounting System
      • IBC vibration isolators
      • Mounting base types
      • Spring type vibration isolators
      • Standard package isolators
    • Power Termination
      • Circuit breakers, IEC compliant
      • Circuit breakers, UL listed
    • Power Connections
      • Low voltage connection cables
      • Neutral grounding connection
      • Center post busbars
    • Starting / Charging System
      • 10 Amp enclosure Battery charger
      • Space heater
      • 10 Amp Battery charger
      • 20 Amp Battery charger
      • 35 Amp Battery charger
      • Electric starting motor - Standard/heavy duty
      • Standard 24 volt open package battery set - Dry
      • Jacket water heater
    • Special Tests / Reports
      • PGS Test report @ 1.0 power factor
      • Standard engine test
      • Generator test report
      • Custom generator TVA report
      • PGS Test report @ 0.8 power factor
      • CSA test and certification
      • IBC seismic Certifications
      • Standard genset Torsional Vibration Analysis (TVA) report
      • OSHPD seismic Certifications
    • General
      • Special paint
      • US aid emblem