C4.4 Generator Set
Maximum Rating
110 kVA
Minimum Rating
50 kVA
Emissions/Fuel Strategy
EU Stage II & R96/EUIIIa
SPECIFICATIONS
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Engine Specifications
Engine Model
Cat® C4.4
Bore
4.1 in
105 mm
Stroke
5 in
127 mm
Displacement
268.5 in³
4.4 l
Compression Ratio
16.2:1, 17.25:1, 18.2:1 or 18.3:1
Aspiration
Turbocharged
Fuel System
Direct Injection or Common Rail
Governor Type
Mechanical
Generator Set Dimensions
Length - Maximum
75.8 in
1,925 mm
Width - Maximum
44.1 in
1,120 mm
Height - Maximum
53.6 in
1,361 mm
Generator Set Specifications
Maximum Rating
110 kVA
Minimum Rating
50 kVA
Emissions/Fuel Strategy
EU Stage II & R96/EUIIIa
Voltage
110 to 480 Volts
Frequency
50 Hz
Speed
1500 rpm
Duty Cycle
Standby, Prime
- Air Inlet System
- Air cleaner; light duty with disposable element
- Cooling System
- Coolant drain line with valve
- Caterpillar extended life coolant
- Radiator and cooling fan with guards
- Fan drive, battery charging alternator drive
- Exhaust System
- Stub pipe, gaskets, raincap and SAE exhaust flange for customer use - shipped loose
- Fuel System
- Standard open set fuel tank/base supplied base, formed steel with single wall integral 8-hour fuel tank
- Control Panel
- GCCP 1.3
- Generators and Attachments
- Voltage regulator (single phase sensing)
- Tower panel, IP22, bottom cable entry
- IP23 Protection
- Circuit breaker, IEC, 3 pole, mounted in tower panel
- 12 Leads
- Segregated low voltage (AC/DC) wiring panel
- Governing System
- Mechanical and electrical governing system - model dependent
- Mounting System
- Captive linear vibration isolators between base and engine-generator
- Includes lifting provision and drag points
- Termination points for coolant and lube oil drain lines
- Starting/Charging System
- Batteries
- 24V battery with rack and cables
- General
- Engine and alternator pre-paint, Caterpillar yellow
- Lube System
- Oil drain line with valve
- Lubricating oil
- Alternator System
- 3 phase sensing
- Anti-condensation heater
- R Frame auxilliary winding
- LC Frame alternator
- Quadrature droop kit
- Permanent magnet excitation (PMG)
- LC Frame alternator with coastal insulation protection
- Circuit breakers
- Circuit breaker upgrades - 4 Pole circuit reaker to 250A, 400A and 630A
- Cooling System
- Coolant heater
- Low coolant temperature alarm
- Low coolant level shutdown
- Control Panels
- GCCP 1.3
- Control Panel Options
- Earth fault (2 wire only)
- Enclosures
- Sound attenuated Level 2 enclosure
- Rental pack - CAE rental option only
- Socket blanking plate - CAE rental option only
- CEE form sockets - CAE rental option only
- Sound attenuated Level 1 (galv)
- European Certifications
- Upgrade to STD set for CE
- Fuel System Accessories
- High fuel level alarm
- Low fuel level shutdown
- Skidbase for CALG enclosure sets
- Bunded fuel tank
- Low fuel level alarm
- Open set narrow tankbase
- Compact skidbase for open set
- Global Certifications
- Certification for CIS
- Mounting Options
- Silencer installation kit
- Electronic governor
- Residential siliencer
- External single point lift - enclosure
- Battery removal
- Industrial silencer
- Power Termination
- Circuit breakers, UL listed
- Special Packing/Inspectons for Shipment
- PGS Test report @ 1.0 power factor
- PGS Test report @ 0.8 power factor
- General - Accessories / Miscellaneous
- Stone guards/rad trans flange
- Packing case - canopied set
- Packing case - compact set
Similar Models
WHY CHOOSE EMPIRE
-
Machines built tough and ready to run in rugged applications
-
Trusted advisors to help you find and maximize your equipment
-
Wide inventory of rental equipment that lets you try before you buy
-
Full service and support to ensure performance and longevity