THIS IS MY SELECT

Diesel Generator Sets

D60 GC Generator Set

Maximum Rating

60 ekW

Minimum Rating

60 ekW

Emissions/Fuel Strategy

U.S. EPA Cert., Tier 3

SPECIFICATIONS

Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.

    Engine Specifications

    Engine Model

    C4.4, In-line 4, 4-cycle diesel

    Bore

    4.1 in

    Stroke

    in

    Displacement

    269 in

    Compression Ratio

    16.7:1

    Aspiration

    Turbocharged

    Fuel System

    Electronic (adjustable)

    Governor Type

    Mechanical, ADEM™A4

    Generator Set Dimensions

    Length - Maximum

    77.2 in

    Width - Maximum

    43.3 in

    Height - Maximum

    48 in

    Dry Weight - Genset (maximum)

    2,054 lb

    Generator Set Specifications

    Maximum Rating

    60 ekW

    Minimum Rating

    60 ekW

    Emissions/Fuel Strategy

    U.S. EPA Cert., Tier 3

    Voltage

    208 to 600 Volts

    Frequency

    60 Hz

    Speed

    1800 rpm

    Duty Cycle

    Standby

    • Certificates
      • IBC Seismic and Wind Certifications
    • Air Inlet System
      • Air Cleaner
      • Cartridge type air filter
    • Circuit Breakers
      • Breakers (100% UL rated)
      • 3-Pole 100% rated
      • Second circuit breaker box
      • Power perminal strips
    • Charging System
      • NFPA battery charger UL10A 120VAC
    • Control Panel
      • GCCP 1.2 Control panel
    • Exhaust System
      • Stub pipe, gaskets, raincap and SAE exhaust flange for customer use - shipped loose
    • Fuel System
      • Standard open set fuel tank / base supplied base, formed steel with single wall integral 24-hour fuel tank
    • Control Panels
      • WSS1 Low coolant level shut down
      • FSS low fuel level alarm & indication panel circuitry required when sub-base tank is selected
      • NFPA110 bundle includes:
      • WCA1 Low coolant temperature alarm
      • A coolant heater, remote annunciator or 0.8 power factor test may be required depending on the application
      • PBC10NU NFPA Battery Charger
      • Oil temperature guage and sender
      • PAA1 Panel mounted audible alarm
      • Ground fault relay
      • Remote E-stop button
      • Remote annunciator
      • Audible alarm
      • Volt free contacts genset run and common alarm
      • Discrete I/O module
      • Overload shutdown via breaker
      • Low coolant temperature alarm
      • Protective devices:
      • Fuel level reading
      • Low coolant level shutdown
    • Cooling System
      • Coolant drain line with valve
      • Fan drive, battery charging alternator drive
      • Caterpillar extended life coolant
      • Radiator and cooling fan with guards
      • Radiator stone guard
    • Generator
      • 12 Leads
    • Governing System
      • Mechanical and electrical governing system - model dependent
    • Lube System
      • Oil drain line with valve
      • Lubricating oil
    • General
      • Engine and alternator pre-paint, Caterpillar Yellow
    • Starting/Charging System
      • Batteries
      • 24V battery with rack and cables

    • Certificates
      • IBC Seismic and Wind Certifications
    • Alternator System
      • R frame auxilliary winding
    • Air Inlet System
      • Cartridge type air filter
    • Charging System
      • NFPA battery charger UL10A 120VAC
    • Circuit Breakers
      • Breakers (100% UL rated)
      • 3-Pole 100% rated
      • Second circuit breaker box
      • Power perminal strips
    • Control Panels
      • NFPA110 bundle includes: FSS low fuel level alarm & indication panel circuitry required
        when sub-base tank is selected - WSS1 Low Coolant level shut down - WCA1 Low Coolant temperature alarm - PAA1 Panel mounted audible alarm - PBC10NU NFPA Battery Charger - A coolant heater ,remote annunciator or 0.8 power factor test may be required depending on the application
      • Ground fault relay
      • Remote E-stop button
      • Volt free contacts genset run and common alarm
      • Oil temperature guage and sender
      • Audible alarm
      • Remote annunciator
      • Protective devices: Low coolant temperature alarm - Low coolant level shutdown - Fuel level reading - Overload shutdown via breaker
      • Discrete I/O module
    • Cooling System
      • Radiator transition flange
    • Enclosures
      • Sound attenuated enclosure, level 1
      • External emergency stop
      • Sound attenuated enclosure, level 2
      • Panel viewing window
    • Exhaust System
      • 10, 25 and 35 dBA silencer systems
      • Overhead silencer mounting kit
    • Fuel System
      • Emergency vent pipe
      • Tank riser
      • 5 gallon spill containment
      • 209 and 394 gallon sub-base fuel tanks
      • 5 gallon fill containment
    • Heating Elements
      • Battery heater
      • Jacket water heater
      • Coolant heater
      • Anti-condensation heater
      • Wiring for canopy space heater
      • Lube oil sump heater
    • Generators
      • Permanent magnet generator
      • Cat Alternator
    • Mounting System
      • Seismic vibration isolators
    • Tests
      • 4 Hour factory test
      • Generator test report
      • PGS test report @ 0.8 power factor
      • PGS test report @ 1.0 power factor

    Similar Models

    WHY CHOOSE EMPIRE

    • Machines built tough and ready to run in rugged applications

    • Trusted advisors to help you find and maximize your equipment

    • Wide inventory of rental equipment that lets you try before you buy

    • Full service and support to ensure performance and longevity

    YOU MIGHT ALSO BE INTERESTED IN