THIS IS MY SELECT
D80 GC Generator Set
Maximum Rating
80 ekW
Minimum Rating
80 ekW
Emissions/Fuel Strategy
U.S. EPA Cert., Tier 3
SPECIFICATIONS
Caterpillar is leading the power generation marketplace with Power Solutions engineered to deliver unmatched flexibility, expandability, reliability, and cost-effectiveness.
Engine Specifications
Engine Model
C4.4, In-line 4, 4-cycle diesel
Bore
4.1 in
105 mm
Stroke
5 in
127 mm
Displacement
269 in³
4.4 l
Compression Ratio
16.7:1
Aspiration
Turbocharged
Fuel System
Common Rail
Governor Type
Mechanical, ADEM™A4
Generator Set Dimensions
Length - Maximum
82.6 in
2,097 mm
Width - Maximum
43.3 in
1,100 mm
Height - Maximum
52.9 in
1,343 mm
Dry Weight - Genset (maximum)
950 lb
2,095 kg
Generator Set Specifications
Maximum Rating
80 ekW
Minimum Rating
80 ekW
Emissions/Fuel Strategy
U.S. EPA Cert., Tier 3
Voltage
208 to 600 Volts
Frequency
60 Hz
Speed
1800 rpm
Duty Cycle
Standby
- Air Inlet System
- Air cleaner; light duty with disposable element
- Air cleaner
- Cooling System
- Radiator and cooling fan with guards
- Fan drive, battery charging alternator drive
- Caterpillar extended life coolant
- Coolant drain line with valve
- Control Panel
- GCCP 1.2 Control panel
- Exhaust System
- Stub pipe, gaskets, raincap and SAE exhaust flange for customer use - shipped loose
- Fuel System
- Standard open set fuel tank/base supplied base, formed steel with single wall integral 24-hour fuel tank
- Generator
- Circuit breaker, IEC, 3 pole, mounted in tower panel
- Voltage regulator (single phase sensing)
- IP23 Protection
- Segregated low voltage (AC/DC) wiring panel
- 12 Leads
- Tower panel, IP22, bottom cable entry
- Governing System
- Mechanical and electrical governing system - model dependent
- Lube System
- Lubricating oil
- Oil drain line with valve
- Mounting System
- Includes lifting provision and drag points
- Termination points for coolant and lube oil drain lines
- Captive linear vibration isolators between base and engine-generator
- Starting/Charging System
- Batteries
- 24V battery with rack and cables
- General
- Engine and alternator pre-paint, Caterpillar yellow
- Alternator System
- 3 Phase sensing
- Anti-condensation heater
- R Frame auxilliary winding
- Permanent magnet excitation (PMG)
- Circuit breakers
- Circuit breaker upgrades - 4 Pole circuit reaker to 250A, 400A and 630 A
- Cooling System
- Low coolant level shutdown
- Coolant heater
- Low coolant temperature alarm
- Control Panel Options
- Earth fault (2 wire only)
- Overload shutdown via breaker
- Earth leakage (2 wire only)
- Volt free contacts
- Panel mounted audible alarm
- Battery charger
- GCCP 1.2 Control panel
- Control panel heater
- Voltage adjust potentiometer
- Emergency stop with key
- Speed adjust potentiometer
- Enclosures
- Sound attenuated Level 2 enclosure
- Fuel System
- High fuel level alarm
- Open set narrow tankbase
- Low fuel level alarm
- Bunded fuel tank
- Low fuel level shutdown
- Compact skidbase for open set
- Skidbase for CALG enclosure sets
- Global Certifications
- Certification for CIS
- Mounting Options
- Battery removal
- Industrial silencer
- Electronic governor
- External single point lift - enclosure
- Silencer installation kit
- Special Packing/Inspectons for Shipment
- PGS Test report @ 1.0 power factor
- PGS Test report @ 0.8 power factor
- General - Accessories / Miscellaneous
- Stone guards/rad trans flange
- Packing case - canopied set
- Packing case - compact set
Similar Models
WHY CHOOSE EMPIRE
-
Machines built tough and ready to run in rugged applications
-
Trusted advisors to help you find and maximize your equipment
-
Wide inventory of rental equipment that lets you try before you buy
-
Full service and support to ensure performance and longevity